NEMA code states that a breaker should allow for a 10-15% variance in amperage for surges, etc. For example, if a kiln draws 30 amps at a full ramp, the breaker should allow for 33-36 amps of space/variance on the circuit or breaker. This means the breaker needs to be at least 40 amps since there is just NO room on a 30 amp breaker for a 30 amp draw. Also if the breaker is too small, it can be a fire hazard due to the amount of heat that will be created.With that in mind, here is a quick checklist of things to troubleshoot:
- Go to the breaker box.... is the correct breaker installed?
- Are you plugged directly into the wall receptacle? NO extension cords allowed!
- What program are you using? Is the ramp speed too slow?
- Turn off kiln and then on again. Put in a program with one segment... Ramp FULL/9999 to 1500F hold 10 min. How long did it take to reach 1500F? Did it reach temp? (larger kilns take longer to heat than smaller ones. A larger kiln may only be able to heat at 400-500 dph.
- Do you have a multi-meter to check the voltage of the line too assure you are getting the full amperage you need?


